Air Differential Pressure Switch
Overview
BCS-2S series air differential pressure switches are mainly used for monitoring the status of air flow such as filter screens, fans in ventilation systems. It has adjustable characteristics and can intuitively adjust the action value of the pressure switch according to the actual on-site situation.
Features
• Multiple measuring ranges optional
• Long service life
• Simple installation and operation
Product Models and Main Parameters
|
Product Model |
Application |
Output Signal |
Measuring Range |
Accuracy |
Media Temperature |
Maximum Working Pressure |
Electrical Parameters |
|
BCS-2S2U-1 |
Air, non-flammable and non-corrosive gas |
Passive switch |
20~200Pa, 10Pa step |
≤±15%, min ±10Pa |
-20℃~85℃ |
10kPa |
Max working pressure 10kPa, 1.5A (0.4A) /250VAC |
|
BCS-2S2U-2 |
Air, non-flammable and non-corrosive gas |
Passive switch |
40~400Pa, 20Pa step |
≤±15%, min ±10Pa |
-20℃~85℃ |
10kPa |
Max working pressure 10kPa, 1.5A (0.4A) /250VAC |
|
BCS-2S2U-3 |
Air, non-flammable and non-corrosive gas |
Passive switch |
100~1000Pa, 50Pa step |
≤±15%, min ±10Pa |
-20℃~85℃ |
10kPa |
Max working pressure 10kPa, 1.5A (0.4A) /250VAC |